Fujitsu Wiring Guidelines

To make Fujitsu air conditioners smart, a Fujitsu protocol converter needs to be installed.

The system topology diagram is shown in the figure below:

Connect the X and Y terminals of the Fujitsu protocol converter to the X1 and X2 terminals of the indoor or outdoor unit of the air conditioner. The A and B terminals of the Fujitsu protocol converter are connected to the X and Y terminals of the TIS-VRF-AC.

Let's talk about the debugging process of the Fujitsu protocol converter:

     (1) Ensure that the internal and external units of the air conditioner are powered on and working normally, and the protocol converter and TIS-VRF-AC are powered on.

     (2) The orange and green lights of the protocol converter flash alternately, wait for about one minute, the green light is always on, and the initialization of the protocol converter is completed.

     (3) At this time, the DIP dial 4 of the Fujitsu protocol converter is set to ON, blue, red, orange, green, etc. flash at the same time, and the protocol converter starts to search for the air conditioner.

     (4) Wait until the blue light is always on, and the other three lights are flashing (the number of lights and the frequency of flashing are different according to the number of air conditioners), and the protocol converter completes the process of searching for air conditioners.

     (5) After the Fujitsu protocol converter completes the search for the air conditioner, dial 4 to return to the original state.

Note: When upgrading the firmware of TIS-VRF-AC, the air conditioner chooses Fujitsu-protocol converter

हम सामग्री को व्यक्तिगत बनाने, विज्ञापन को अनुरूप और विश्लेषण करने तथा साइट के सुरक्षित उपयोग को सुनिश्चित करने के लिए कुकीज़ का उपयोग करते हैं। इस साइट पर क्लिक करके या नेविगेट करके, आप www.tiscontrol.com और कुकीज़ का उपयोग करके संग्रहीत जानकारी के संग्रह के लिए सहमति देते हैं। अधिक जानकारी दस्तावेज़ में उपलब्ध है: गोपनीयता नीति